Model |
RF-25K/P |
RF-33K/P |
RF-46K/P |
RF-70K/P |
ARG-05SK |
ARG-10SB |
Outdoor Unit Air Outlet |
Side Air Outlet |
Up Air Outlet |
Rated Heat Production Capacity |
KW |
3.5 |
4.9 |
6.9 |
9.8 |
17.5 |
35 |
BTU/h |
11900 |
16700 |
23500 |
33500 |
59500 |
119000 |
Rated Outlet
Water Temp. |
℃ |
55 |
Max. Outlet
Water Temp. |
℃ |
60 |
Rated Water Heating Capacity |
L/h |
75 |
110 |
150 |
220 |
375 |
750 |
Rated Input |
KW |
0.91 |
1.36 |
1.75 |
2.5 |
4.6 |
9.2 |
Rated Working
Current |
A |
4.2 |
6.3 |
8 |
11.3 |
13.5 |
27 |
COP |
W/W |
3.8 |
3.9 |
3.9 |
3.9 |
3.8 |
3.8 |
Power Supply |
V/PH/HZ |
220~240V/1PH/50HZ |
380~415V/3PH/50HZ |
Compressor QTY |
Unit |
1 |
1 |
1 |
1 |
1 |
2 |
Compressor Brand |
|
Panasonic |
Copeland |
Fan QTY |
Unit |
1 |
1 |
1 |
1 |
1 |
2 |
Sound Level |
dB(a) |
55 |
55 |
56 |
58 |
61 |
63 |
Water Inlet/Outlet
Diameter |
Inch |
3/4" |
3/4" |
3/4" |
3/4" |
1" |
5/4" |
Water Inlet/Outlet
Direction |
|
Left |
Right |
Left |
Right |
Applied Water Pump Flow Capacity |
m3/h |
1.2~2.5 |
1.8~3.2 |
2.2~3.8 |
3~4.5 |
5~8 |
10~15 |
Water Pump Installation |
|
Internal Circulation Pump (inside the unit) |
External Circulation Pump (Optional) |
Water-Refrigerant Heat Exchanger |
Shell Type Heat Exchanger |
Shell Type Heat Exchanger |
Flat Panel Heat Exchanger |
Refrigerant |
|
R22 or R417a |
Outline Dimension |
L |
mm |
850 |
980 |
980 |
1050 |
740 |
1480 |
W |
330 |
350 |
350 |
350 |
746 |
845 |
H |
540 |
550 |
550 |
620 |
940 |
1300 |
Packing Dimension |
L |
mm |
910 |
1090 |
1090 |
1160 |
820 |
1630 |
W |
340 |
380 |
380 |
380 |
765 |
980 |
H |
575 |
590 |
590 |
660 |
1140 |
1450 |
Weight |
N.W. |
kg |
35 |
58 |
60 |
68 |
108 |
255 |
G.W. |
38 |
61 |
63 |
71 |
123 |
285 |
Remark |
Rating values above are in accordance with the average value from GB testing condition "Air Source Heat Pump testing condition-nominal testing condition" as following:
1.Dry-bulb temperature:20℃
2.Wet-bulb temperature:15℃
3.Water 15℃ in 55℃ out. |